SECTION 4 – SYSTEM PLANNING
2014-MAY-02 REV. 0 PAGE 4-11
PLANNING CHECKLIST TEMPLATE
(Copy before use)
Components
h
CHECKFIRE 210 Display Module
h
Mounting Bracket
h
Display Cable
h
CHECKFIRE 210 Interface Control Module
h
Detection Circuit Cable(s), Tees, EOL Device, and Branch
Terminator(s)
h
Electric Manual Actuator(s) (EMA) and Bracket(s)
h
Linear Detector(s)
h
Spot Thermal Detector(s) (include bracket and heat shield),
if applicable
h
Release Circuit Cable(s) and Tees
h
Release Circuit Drop Cable(s)
h
PAD(s)
h
Electric-Pneumatic Actuator(s) (may be supplied with agent
tanks)
h
Pneumatic Manual Actuator(s) (optional)
h
Relay Circuit #1 and #2 Cable(s)
h
Auxiliary Output Cable(s)
h
Power Circuit Cable(s) and Fused Power Circuit Cable
h
Pressure Switch(es), if applicable
h
Rubber-Coated 5/16 in. (8 mm) P-Clamps (by others)
h
Double-Loop Cable Ties
h
Bulkhead Connectors (display, detection, release, and
power circuits)
h
Alarms and/or Strobes
h
Label Package
Note:
For part numbers, see Section 10 – Appendix, Compo
-
nent Index, page 10-1.
Programming Options
(Certain options will affect availability of other options)
Pressure Switch Feedback (PSF)
h
Disabled (default)
h
Enabled, uses Detection Circuit #2 for pressure switch
input.
h
Enable auto-release activation of PAD(s)
Note: Cross-Zone not available
Cross-Zone Protection
h
Disabled (default)
h
Enabled, Detection Circuit #1 and #2 are independent
detection and both must detect alarm condition to start time
delays.
Note:
Pressure Switch Feedback not available
Detection Circuit #1 (Cross-Zone disabled)
h
Independent detection/release (default)
h
Detection (Alarm Only)
Detection Circuit #2 (Cross-Zone disabled)
h
Independent detection/release (default)
h
Detection (Alarm Only)
Detection Circuit #2 (Pressure Switch Feedback enabled)
h
Alarm Only (default)
h
Release activation (PADs)
Time Delay #1 (Seconds)
h
0
h
5
h
10 (default)
h
15
Time Delay #2 (Seconds)
h
0
h
5
h
10 (default)
h
15
Time Delay #1 (Restarts)
h
2 (default)
h
Unlimited
Relay Circuit #1
h
Alarm (default)
h
Fault
Relay Circuit #2
h
Shutdown (default)
h
Alarm
CHECKFIRE 210