SECTION 3 – USER INTERFACE
2014-MAY-02 REV. 0 PAGE 3-5
DISPLAY MODULE FRONT PANEL INDICATORS
(Continued)
Shutdown LED (See Figure 3-3)
• Pulses REd 4 x 1 second in an alarm condition beginning in
the last 5 seconds of TD1 (see Table 3-1)
• Illuminates REd steady-on in the last second of td1 (see
Table 3-1)
• Pulses REd 4 x 1 second during td2
• Indicates Release activated and Post Release activated
conditions (see Table 3-1)
INTERNAL SOUNDER (AUDIBLE NOTIFICATION)
• audible notification for all alarm and fault conditions, except
for external fault in a dual power system.
• Pulses at same rate as a corresponding lEd indicator(s)
(see Table 3-1), unless silenced
• Minimum 85 dB at 3.3 ft (1 m)
DISPLAY MODULE MOUNTING
Two types of mounting options are available.
• suRFaCE Mount – display Module includes integral
index pins, foam gasket, rubber washer and securing nut to
fasten the display module in place without a bracket. the
foam gasket minimizes moisture and dust ingress though the
opening.
• BRaCkEt Mount - the optional Mounting Bracket (Part
no. 439564) is constructed of durable high-strength glass-
filled nylon material. The pivot and secure feature accommo-
dates easy operator visual identification and access to the
CHECKFIRE 210 Display Module for status indications and
manual operation. See Figure 3-4.
Note: The display module should never be mounted in an area
subject to pressure washing or steam cleaning.
FIGURE 3-4
DISPLAY MODULE BRACKET
009181
POWER
Internal Power
The CHECKFIRE 210 System has an internal power source
(ICM Battery Module (Part no. 440352)) providing up to 365
days of power under normal operating conditions. The Power
LED pulses GREEn 1 x 3 seconds for internal power. The
battery module is supervised for low power conditions when
operating independently.
External Power
The CHECKFIRE 210 System may use equipment power as
the external power source. The Power LED illuminates GREEn
steady-on for external power. The external power circuit
requires 12/24 VDC nominal and is supervised for low power
conditions.
Dual Power
when both external power and internal power are connected,
the internal power source serves as the reserve power source.
CHECKFIRE 210
Detection and Actuation System