SECTION 3 – USER INTERFACE
2014-MAY-02 REV. 0 PAGE 3-1
USER INTERFACE
This section provides the user with overall information on
features and operation of the CHECKFIRE 210 Display Module
and Interface Control Module (ICM).
FIELD CONNECTIVITY – Cables and Devices
The CHECKFIRE 210 ICM communicates with the Display
Module and other devices through cable assemblies incor-
porating IP67 circular threaded connectors with color-coded
overmolding.
IP67 is an environmental ingress protection rating. The first
number indicates protection from solid objects (0 is no special
protection, 6 is protection from dust). The second number is
protection against liquids (0 is no protection, 7 is protection
against the effect of immersion in water).
Display Cable (See Figure 3-2)
• 24 in. (610 mm) Cable
• Black color-coded IP67 anti-vibration connector (Female)
FIGURE 3-1
DISPLAY CABLE
009272
DISPLAY MODULE FRONT PANEL BUTTONS
“DELAY/Reset/Silence” Button
Manage fault and/or alarm conditions by pressing the “DELAY/
Reset/Silence” button (see Figure 3-2) for the following results:
• Audible Fault Silence
o Silence an audible notification during a fault condition for
two hours. Fault LED indicator(s) continue pulsing until the
fault condition has been cleared.
o During a post-release condition the button will silence the
sounder.
o Any new alarm or fault conditions will reactivate the
audible notification.
o The audible notification for either a post-release or fault
condition will resume after being silenced for two hours.
• Restart Time Delay Sequence
Restart the time delay cycle during an alarm condition; must
be initiated before Time Delay #1 (TD1) period expires.
• System Reset
Press and hold (3 seconds) to reset the system.
FIGURE 3-2
DISPLAY MODULE FRONT PANEL BUTTONS
009290
CHECKFIRE 210
Detection and Actuation System
“PuSH To ACTIVATE/ALARM wHEn LIT”
Button and REd lEd IndICatoR
“DELAY/RESET/
sIlEnCE” Button
DISPLAY
CaBlE
BlaCk
ConnECToR