4. Set DCT switch to “Alarm” position. Confirm Red Detec-
tion 1 LED, Red “Push to Actviate / Alarm When Lit” LED
and sounder pulse 1 x 1 second; Amber Isolate LED and
sounder pulse 2 x 30 seconds.
Verify time delays do not start.
5. After 30 seconds of indication, open the protective guard
door and push the “PUSH to Activate / Alarm When Lit”
button. Release Activated starts immediately.
Note: There is no time delay upon manual activation.
6. Release Activated – The Red “PUSH to Activate / Alarm
When Lit” LED, Red Shutdown LED, Red Detection 1
LED, and sounder are steady-on for 10 seconds; Amber
Isolate LED pulses 2 x 30 seconds.
7. Post Release Activated – The Red Shutdown LED, Red
Detection 1 LED, and sounder pulse 1 x 10 seconds; and
Amber Isolate LED and sounder pulse 2 x 30 seconds.
8. Push the “DELAY/Reset/Silence” button to test sounder
silence. Sounder silences and LEDs continue.
SECTION 6 – OPERATIONAL TEST AND PLACE IN SERVICE
2014-MAY-02 REV. 0 PAGE 6-5
CHECKFIRE 210
Detection and Actuation System
TABLE 6-2: ISOLATION FEATURE (External or Dual Power Only) (Continued)
009290
ALARM CONDITION
DCT = ALARM
RED/AMBER LEDs
AND SOUNDER
PULSE
1 X 1 SECOND,
AMBER LED PULSES
2 X 30 SECONDS
VERIFY TIME
DELAYS
DO NOT START
009290
RELEASE
ACTIVATED
RED LEDs AND
SOUNDER
STEADY-ON FOR 10
SECONDS, AMBER
LED PULSES
2 X 30 SECONDS
PUSH RED BUTTON
009290
POST RELEASE
ACTIVATED
RED LEDs AND
SOUNDER PULSE
1 X 1 SECOND,
AMBER LED PULSES
2 X 30 SECONDS
PUSH BUTTON
SOUNDER STOPS