SECTION 3 – USER INTERFACE
PAGE 3-2 REV. 0 2014-MAY-02
DISPLAY MODULE FRONT PANEL BUTTONS (Continued)
Red “PUSH To Activate / Alarm When Lit” Button and LED
Indicator (See Figure 3-2)
• Combination button and lEd indicator
• Manual aCtIVatIon - Pressing the red “PusH to acti
-
vate / alarm When lit” Button immediately activates the
release circuit and illuminates the red LED for 10 seconds.
Note: no time delay occurs when red “PuSH To Activate /
alarm When lit” Button is pressed.
After 10 seconds, the system enters Post Release Activated
mode.
• dEtECtoR aCtIVatIon - the “PusH to activate / alarm
when Lit” LED indicator displays the conditions listed in
Table 3-1.
PRE-ALARM ConDITIon (PREVIouS To TD1)
LED pulses RED 1 x 1 second during an alarm only or first
alarm condition with Cross-Zone programming or alarm condi-
tion in Isolate Mode.
ALARM ConDITIon:
Time Delay #1 (TD1)
LED pulses RED 2 x 1 second until last 5 seconds of Time
Delay #1 (TD1) period (sounder matches pulse rate).
In last 5 seconds of TD1, LED pulses RED 4 x 1 second for
4 seconds; in the final second LED is off (sounder matches
shutdown LED pulse rate).
Time Delay #2 (TD2)
LED pulses RED 4 x 1 second until Time Delay #2 (TD2)
period expires (sounder matches pulse rate).
Release Activated
LED illuminates RED and remains steady-on for 10 seconds
(release circuit active) (sounder remains steady-on).
Post Release Activated
no LED indication (sounder matches other LED indications).
CHECKFIRE 210
Detection and Actuation System