SECTION 5 – INSTALLATION ANd prOgrAmmINg
2014-MAY-02 REV. 0 PAGE 5-27
TABLE 5-3: mANUAL prOgrAmmINg OpTIONS (Continued)
CHECKFIRE 210
Detection and Actuation System
Td1-5 and Td1-6, Time delay #1 (Td1) programming
TD1 is the delay period between an alarm condition and TD2.
TD1-5 and TD1-6 change Time Delay #1 (TD1) between the
standard 10 seconds (default programming – TD1-5 OFF,
and TD1-6 OFF) and 0, 5 or 15 seconds. Modifications made
to TD1 do not affect the duration of Time Delay #2 (TD2).
1. Review system plan to determine value for TD1 (see
below table for options). Push programming button as
needed to select TD1-5 or TD1-6 to make appropriate
adjustments to either LED.
Seconds
Td1-5
Td1-6
0
ON
ON
5
ON
OFF
10
OFF
OFF (default)
15
OFF
ON
2. Press and hold the programming button for more than
1 second to turn ON or OFF either LED to match the
required time value.
3. Push the programming button to move to TD2-7 and
confirm TD1-5 and TD1-6 are programmed correctly (see
above table) and TD2-7 is pulsing 1 x 1 second.
4. Save the ICM programming change.
Reset to Normal: Press and hold “DELAY/Reset/
Silence” button for 3 seconds; Green and Red LEDs are
steady-on for 1 second; then Amber LEDs are steady-on
for 1 second; at end sounder quickly pulses 3 times.
CAUTION
TD1 is the delay period between an alarm condition and
equipment shutdown. If using the shutdown relay function,
programming TD1 to zero seconds results in immediate
equipment shutdown and immediate start of TD2 upon initia-
tion of an alarm condition.
CAUTION
!
Programming both Time Delay #1 and Time Delay #2 to zero
seconds results in immediate System activation following an
alarm condition. This situation could lead to immediate equip-
ment shutdown (if using the shutdown relay function) or other
unforeseen issues which could result in significant property
damage or personal injury.
1. PUSH PB
UNTIL
TD1-5 OR
TD1-6 IS
SELECTED
2. PRESS
AND HOLD
PB TO
CHANGE
SETTING:
3. PUSH PB
TO MOVE
TO NExT LED
AND CONFIRM
CHANGE IS
CORRECT
4. SAVE CHANGE
009322
0 SEC.
5 SEC.
10 SEC.
15 SEC.