SECTION 6 – OPERATIONAL TEST AND PLACE IN SERVICE
PAGE 6-16 REV. 0 2014-MAY-02
CHECKFIRE 210
Detection and Actuation System
TABLE 6-3: OPERATIONAL TEST (Continued)
Electric Manual Actuator (EMA) Test (Continued)
5. Reset EMA by pulling red strike button up to set position,
re-install ring pin. Do not reseal at this time.
6. Reset RCT.
7. Reset to Normal: Press and hold “DELAY/Reset/
Silence” button for 3 seconds; Green and Red LEDs are
steady-on for 1 second; then Amber LEDs are steady-on
for 1 second; at end sounder quickly pulses 3 times.
8. Repeat Test for each remaining EMA following above
steps.
CAUTION
If the system includes Pneumatic Manual Actuator(s), test
these components separately in accordance with the appro-
priate system manual (latest edition):
LT-A-101-10/20/30 Manual (Part No. 24327)
LT-A-101-50/125/250 Manual (Part No. 427865)
LVS Manual (Part No. 427109)
The actuators also have ring pins and red strike buttons.
Actuation can cause fire suppression system release.
009290
RETURN TO
NORMAL STATUS
RESET RCT, AND
MODULE
POWER LED IS
GREEN STEADY-ON
RESET EMA:
PULL RED BUTTON UP,
INSERT RING PIN
009217