SECTION 5 – INSTALLATION ANd prOgrAmmINg
2014-MAY-02 REV. 0 PAGE 5-29
TABLE 5-3: mANUAL prOgrAmmINg OpTIONS (Continued)
CHECKFIRE 210
Detection and Actuation System
Tdr-9, Time delay restarts for Td1
TDR-9 changes the number of times TD1 can be restarted
from the display module between 2 restarts (default program-
ming – OFF) and unlimited restarts (ON). TD1 is the time
delay period between an alarm condition and TD2.
1. If the system plan requires unlimited restarts and TDR-9
is OFF, push programming button until TDR-9 is selected
(pulsing at a rate of 1 x 1 second).
WArNINg
!
Delay of system operation may allow the fire to intensify,
which could result in a more difficult fire to suppress.
2. Press and hold the programming button for more than
1 second to turn ON TDR-9 and specify the unlimited
restarts function. The 1 x 1 second pulse is now twice as
long.
3. Push the programming button to move to the next LED
and confirm
• TDR-9 is steady-on
• RLY-10 is pulsing 1 x 1 second.
4. Save the ICM programming change.
Reset to Normal: Press and hold “DELAY/Reset/
Silence” button for 3 seconds; Green and Red LEDs are
steady-on for 1 second; then Amber LEDs are steady-on
for 1 second; at end sounder quickly pulses 3 times.
rLY-10, relay #1, Alarm/Fault
RLY-10 changes the function of Internal Relay #1 between
an Alarm relay (default – OFF) and a Fault relay (ON).
Alarm functionality responds to an alarm condition. when
programmed to the Fault functionality, a fault condition trans-
fers the relay contacts. In both cases, the relay will return to
normal once the alarm condition or fault clears.
1. If the system plan requires Relay #1 to function as a Fault
relay and RLY-10 is OFF, push programming button until
RLY-10 is selected (pulsing at a rate of 1 x 1 second).
2. Press and hold the programming button for more than 1
second to turn ON the LED and specify the Fault relay
function. The 1 x 1 second pulse is now twice as long.
3. Push the programming button to move to the next LED
and confirm
• RLY-10 is steady-on
• RLY-11 is pulsing 1 x 1 second.
4. Save the ICM programming change.
Reset to Normal: Press and hold “DELAY/Reset/
Silence” button for 3 seconds; Green and Red LEDs are
steady-on for 1 second; then Amber LEDs are steady-on
for 1 second; at end sounder quickly pulses 3 times.
1. PUSH PB
UNTIL
TDR-9 IS
SELECTED
2. PRESS
AND HOLD
PB TO
CHANGE
SETTING
3. PUSH PB
TO MOVE
TO NExT LED
AND CONFIRM
CHANGE IS
CORRECT
4. SAVE CHANGE
1. PUSH PB
UNTIL
RLY-10 IS
SELECTED
2. PRESS
AND HOLD
PB TO
CHANGE
SETTING
3. PUSH PB
TO MOVE
TO NExT LED
AND CONFIRM
CHANGE IS
CORRECT
4. SAVE CHANGE