SECTION 9 – TROUBLESHOOTING
PAGE 9-2 REV. 0 2014-MAY-02
CHECKFIRE 210
Detection and Actuation System
TABLE 9-1: POWER LED INDICATIONS (Continued)
AMBER Power LED
Internal or External Power Fault
Amber Power LED and Sounder pulsing 1 x 10 seconds indi-
cating power from the power source dropped below accept-
able level causing a fault condition.
• Check Power Circuit Cable and Fused Power Circuit Cable
for proper connections and for proper voltage
• Confirm fuse is good and installed correctly (See Section
5 – Installation and Programming, page 5-16 for correct
removal and replacement of fuse.)
• Replace cables if unable to clear fault indication
• Check connection of the Battery Module to the ICM battery
cable located under the battery compartment cover.
• Check and replace internal power Battery Module with a
new/unused battery module. See Battery Replacement in
Section 8 – Recharge, Inspection, and Maintenance, page
8-5.
Dual Power Fault
Amber Power LED pulsing 1 x 3 seconds indicating power
from the external power source dropped below acceptable
level causing a fault condition. When external power source
drops below an acceptable level system automatically draws
power from internal battery.
• Check Power Circuit Cable and Fused Power Circuit Cable
for proper connections and for proper voltage
• Confirm fuse is good and installed correctly (See Section
5 – Installation and Programming, page 5-16 for correct
removal and replacement of fuse.)
• Replace cables if unable to clear fault indication
For more information see TABLE 9-7: Specific Circuit
Testing Procedures.
009290
INTERNAL/
EXTERNAL POWER
FAULT
AMBER LED AND
SOUNDER PULSE
1 X 10 SECONDS
009290
DUAL POWER
FAULT
AMBER LED PULSES
1 X 3 SECONDS