SECTION 5 – INSTALLATION ANd prOgrAmmINg
2014-MAY-02 REV. 0 PAGE 5-35
TABLE 5-5: pErSONAL COmpUTEr (pC) OpTIONS (Continued)
CHECKFIRE 210
Detection and Actuation System
modifying programming Options
Each of the options shown in Table 5-1 – Programming
Summary (page 5-22) is programmed using a drop down
menu and clicking the desired options. Certain options will be
grayed out when others are selected. when options turn red,
the programming has not been saved to the ICM.
default programming
Circuit Option
(ICm LEd Identifier)
Function
1. Pressure Feedback (PSF-1)
Disabled
2. Cross-Zone Detection (DET-2)
Disabled
3. Detection Circuit #1 (DET-3)
Release Act.
4. Detection Circuit #2 (DET-4)
Release Act.
5. Time Delay #1 (TD1-5 and TD1-6)
10 sec. delay
6. Time Delay #2 (TD2-7 and TD2-8)
10 sec. delay
7. Time Delay #1 Restarts (TDR-9)
Two restarts
8. Relay #1 (RLY-10)
Alarm
9. Relay #2 (RLY-11)
Shutdown
Alternate programming:
1. Pressure Switch Feedback – Pressure switch communi-
cates to ICM through Detection Circuit #2.
2. Cross-Zone Detection – Requires an alarm condition on
both Detection Circuits #1 and #2 before starting Time
Delay #1 (TD1).
3. Det. Ckt. #1 - Alarm Only – Prohibits start of TD1 count-
down for any alarm condition on Detection Circuit #1.
(Not available when cross-zone detection is enabled.)
4. Det. Ckt. #2 - Alarm Only – Prohibits start of TD1 count-
down for any alarm condition on Detection Circuit #2.
(Not available when cross-zone detection is enabled.)
a.
Alarm Only - System provides release notification, and
does not send release signal to PAD(s) (Default when
Pressure Switch Feedback is enabled)
b.
Release Activation - System provides release notifi
-
cation, and sends release signal to PAD(s)
(Optional
when Pressure Switch Feedback is enabled)
5. Time Delay #1 (TD1) – Optional delay periods (0, 5 or 15
seconds) between an alarm condition and Time Delay #2
(TD2).
6. Time Delay #2 (TD2) – Optional delay periods (0, 5 or 15
seconds) starting after time delay #1 (TD1).
7. Time Delay #1 Restarts - Unlimited restarts.
8. Relay #1 - Fault – Relay contacts transfer on any fault
condition.
9. Relay #2 - Alarm – Relay contacts transfer on an alarm
condition.
RED
HIGHLIGHTING
INDICATES
PROGRAMMING
NOT SAVED
TO ICM
GREYED OUT
DROP DOwN
INDICATES
OPTION NOT
AVAILABLE
009333
FACTORY
DEFAULT
SETTINGS
009332