SECTION 6 – OPERATIONAL TEST AND PLACE IN SERVICE
2014-MAY-02 REV. 0 PAGE 6-9
CHECKFIRE 210
Detection and Actuation System
TABLE 6-3: OPERATIONAL TEST (Continued)
Detection Circuit #1 (and #2): Alarm Condition Test
CAUTION
Before beginning this test, verify:
• Release Circuit Test Plug(s) and RCT are connected in the
Release Circuit.
• DCT replaces the EOL Device in Detection Circuit #1.
• Determine the delay periods of TD1 and TD2 from the
programming options.
1. Simulate alarm condition by turning switch on DCT to
“Alarm” position.
2. If alarm relay is programmed, confirm activation of
connected devices.
3. Verify accuracy of time delay:
a. The Red “PUSH to Activate / Alarm When Lit” LED,
the Red Detection 1 LED, and sounder pulse two
times per second until last 5 seconds of the TD1
period.
In the last 5 seconds of TD1, the Red LEDs listed
above, Red Shutdown LED, and sounder pulse 4 x 1
second for 4 seconds, then only the Red Shutdown
LED is steady-on for the last second.
b. During TD2 period the pulse rate continues at 4 x 1
second.
4. Release Circuit Activation: Upon expiration of both TD1
and TD2 time delays, the Release Circuit activates.
009290
CAUTION
VERIFY RCT AND
DCT INSTALLED!
START OF
DETECTION CIRCUIT
ALARM CONDITION
(DCT = ALARM)
RED LEDs AND
SOUNDER PULSE
2 X 1 SECOND UNTIL
LAST 5 SECONDS
OF TD1 PULSE 4 X 1
SECOND.
009290
5 SECONDS BEFORE
TD1 END,
RED LEDs AND
SOUNDER PULSE
4 X 1 SECOND FOR
4 SECONDS
THEN STEADY-ON FOR
LAST SECOND.
DURING TD2 RED
LEDS AND SOUNDER
PULSE 4 X 1 SECOND.
009290
ONLY SHUTDOWN
LED IS
STEADY-ON FOR
LAST SECOND
OF TD1.
009290
DURING TD2 RED LEDs
AND SOUNDER PULSE
4 X 1 SECOND.