SECTION 6 – OPERATIONAL TEST AND PLACE IN SERVICE
2014-MAY-02 REV. 0 PAGE 6-3
CHECKFIRE 210
Detection and Actuation System
TABLE 6-1: PREPARATION – OPERATIONAL TEST (Continued)
Power Up (External or dual power only) (Continued)
• Reset to Normal: Press and hold “DELAY/Reset/Silence”
button for 3 seconds; Green and Red LEDs are steady-on
for 1 second; then Amber LEDs are steady-on for 1 second;
at end sounder quickly pulses 3 times.
• Power LED is Green steady-on for External or Dual Power
NOTICE
Confirm no other LEDs are pulsing. If fault
or alarm conditions are indicated, refer to
Section 9 – Troubleshooting to clear all condi-
tions prior to performing the operational test.
Power Up (Internal power only)
Before conducting the OPERATIONAL TEST, make certain
internal power is properly connected to CHECKFIRE 210
System.
• Install battery:
1. Remove battery compartment cover.
2. Insert battery into battery well; align connector keyways
and connect battery pigtail with battery cable on the
ICM.
• Reset to Normal: Press and hold “DELAY/Reset/Silence”
button for 3 seconds; Green and Red LEDs are steady-on
for 1 second; then Amber LEDs are steady-on for 1 second;
at end sounder quickly pulses 3 times.
• Power LED pulses Green 1 x 3 seconds for Internal Power
Note: For system running on Internal power only, refer to
Table 6-4: Internal Power Circuit Only – Operational Test, for
specific testing procedures.
NOTICE
Confirm no other LEDs are pulsing. If fault
or alarm conditions are indicated, refer to
Section 9 – Troubleshooting to clear all condi-
tions prior to performing the operational test.
KEY TO DISPLAY MODULE INDICATIONS –
IDENTIFY LEDs AS:
LED STEADY-ON
LED PULSING
LED
(Red or Green)
(Amber, Red or Green)
OFF
BATTERY CABLE
BATTERY
PIGTAIL
009347
009290
RESET TO NORMAL
PRESS AND HOLD 3
SECONDS
LEDs TEST CYCLE
THEN SOUNDER
PULSES 3 TIMES
GREEN LED PULSES
1 X 3 SECONDS
009290
RESET TO NORMAL
PRESS AND HOLD 3
SECONDS
LEDs TEST CYCLE
THEN SOUNDER
PULSES 3 TIMES
LED IS GREEN
STEADY-ON