ICM Programming Panel
Remove the battery cover for access to the programming
button and associated program indicator lights (LEDs). The
mini usB port and battery cable for the internal battery module
are next to the LEDs. See Figure 3-7.
FIGURE 3-7
ICM PROGRAMMING PANEL
009292
System Isolate Switch
The CHECKFIRE 210 System includes an isolation feature
for end-users to minimize the occurrence of a false discharge
when service or maintenance is being performed on the
protected vehicle/equipment (not intended for CHECKFIRE
210 System maintenance).
The System is placed in Isolate Mode by operating the isolate
switch located on the side of the ICM enclosure. while in
isolate mode, the LED and sounder on the Display Module
quickly pulse 2 x 30 seconds. If desired, to silence the sounder
push the “DELAY/Reset/Silence” button. See Figure 3-7.
when placed in Isolate Mode, an automatic detection circuit
input (alarm condition) will not initiate the release circuit.
However, a manual actuation by either an EMA or the “PuSH
to Activate/ Alarm when Lit” button bypasses the isolation
feature and immediately activates the release circuit.
FIGURE 3-7
ICM ISOLATE SWITCH
009277
CHECKFIRE 210
Detection and Actuation System
PRoGRAMMInG
LEDs
MInI usB PoRt
BattERy CaBlE
PRoGRAMMInG
Button
ISoLATE