SECTION 5 – INSTALLATION ANd prOgrAmmINg
2014-MAY-02 REV. 0 PAGE 5-37
CHECKFIRE 210
Detection and Actuation System
EVENT HISTOrY LOg - prOgrAmmINg
The Checkfire 210 System records changes made to System Programming in the Event History Log. Each programming change is
indicated with the message “Configuration Has Been Modified.” The message includes the programming before and after modifica-
tion. Two lines of lower ID sequential numbers before the message list the previous configuration; two lines of higher ID sequential
numbers after the message report the modified configuration. Refer to Table 5-6 – Event History Log Programming Descriptions to
identify the acronyms representing programming options.
For Example: In the sample Event History Log shown above, the System was modified on February 27, 2014 at 8:47 AM. Two
changes were made: Detection Circuit #1 was re-programmed to Alarm Only, and Time Delay #1 was re-programmed from a 10
second delay (default) to a 15 second delay. Remaining programming options were unchanged.
Table 5-6 – Event History Log programming descriptions
position
default
Optional programming
description
1
DET
PSF
DET
Detection Circuit #2 programmed as a detection
circuit
PSF
Programmed for Pressure Switch Feedback.
2
IND
CRZ
IND
Detection Circuits #1 & #2 programmed as detection
circuits
CRZ
Programmed for Cross-Zone Detection
3
RLS #1
ALM #1
RLS #1
Detection Circuit #1 programmed for independent
detection/release
ALM #1
Detection Circuit #1 programmed for Alarm Only
indication
4
RLS #2
ALM #2
RLS #2
Detection Circuit #2 programmed for independent
detection/release
ALM #2
Detection Circuit #2 programmed for Alarm Only
indication
5
TD1=10
TD1= (0,5,15)
TD1=10
Time Delay #1 programmed for 10 seconds (default)
TD1= xx
TD1 programmed for 0, 5, or 15 seconds.
6
TD2=10
TD2= (0,5,15)
TD2=10
Time Delay #2 programmed for 10 seconds (default)
TD2= xx
TD2 programmed for 0, 5, or 15 seconds.
7
TD1RST=2
TD1RST=INF
TD1RST=2 Time Delay #1 programmed for two restarts
TD1RST=INF Time Delay #1 programmed for infinite restarts
8
R1=ALM
R1=FLT
R1=ALM
Relay #1 programmed for Alarm relay
R1=FLT
Relay #1 programmed for Fault relay ()
9
R2=SHDN
R2=ALM
R2=SHDN
Relay #2 programmed for Shutdown relay
R2=ALM
Relay #2 programmed for Alarm relay
AFTER SAVING MODIFICATIONS
BEFORE SAVING MODIFICATIONS