SECTION 6 – OPERATIONAL TEST AND PLACE IN SERVICE
PAGE 6-10 REV. 0 2014-MAY-02
CHECKFIRE 210
Detection and Actuation System
TABLE 6-3: OPERATIONAL TEST (Continued)
Detection Circuit #1 (and #2): Alarm Condition Test
(Continued)
5. Release Activated: The Red “PUSH to Activate / Alarm
When Lit” LED, Red Detection 1 LED, Red Shutdown
LED, and sounder remain steady-on for 10 seconds.
6. Post Release Activated: The Red Detection 1 LED, Red
Shutdown LED, and sounder pulse 1 x 10 seconds.
7. Push the “DELAY/Reset/Silence” button to test sounder
silence. Sounder silences and LEDs continue.
8. Confirm RCT displays “PASS.”
Detection Circuit #1 (and #2): Test Time Delay Restart
1. Reset DCT to “Normal” position.
2. Reset RCT - press reset button.
3. Reset to Normal: Press and hold “DELAY/Reset/
Silence” button for 3 seconds; Green and Red LEDs are
steady-on for 1 second; then Amber LEDs are steady-on
for 1 second; at end sounder quickly pulses 3 times.
After reset, Power LED remains GREEN steady-on.
009290
RETURN TO
NORMAL STATUS
RESET DCT, RCT,
AND DISPLAY
MODULE
POWER LED IS
GREEN STEADY-ON
009290
POST RELEASE
ACTIVATED
RED LEDs AND
SOUNDER PULSE
1 X 10 SECONDS
CONFIRM RCT
DISPLAYS “PASS”
PUSH BUTTON
SOUNDER STOPS
009290
RELEASE
ACTIVATED
RED LEDs AND
SOUNDER REMAIN
STEADY-ON FOR 10
SECONDS