SECTION 6 – OPERATIONAL TEST AND PLACE IN SERVICE
PAGE 6-20 REV. 0 2014-MAY-02
CHECKFIRE 210
Detection and Actuation System
TABLE 6-6: PLACING CHECKFIRE 210 SYSTEM IN SERVICE (Continued)
6. Remove actuator cap on top of Electric-Pneumatic Actua-
tor and retain for future use.
CAUTION
!
When handling the PAD, always point actuating end away
from yourself and others. On electrical initiation, PAD oper-
ates very quickly and a small brass disk forcefully separates
from actuating end. Physical injury may occur from contact
with the actuating pin and/or the detaching disk.
7. Put system in Isolate Mode using the Isolate switch on
the side of the ICM.
8. Write installation date on PAD, DO NOT cover manufac-
turing date on label. Install PAD into Release Circuit Drop
Cable. Verify o-ring is in place on PAD.
NOTICE
The PAD (must be replaced after being
in-service for five years.
a.
The in-service date should be
recorded in installation and main-
tenance records and written on the
PAD label with permanent marker at
the time of installation.
b. The PAD has a 10 year shelf life
when stored in an environmentally
stable location. The 5 year in-service
life may not extend beyond the 10
year shelf life. (The month and year
of manufacture is printed on the label
located on the PAD body).
Install all PADs in the Release Circuit Drop Cable(s).
9. Attach Release Circuit Drop Cable to Electric-Pneumatic
Actuator, hand-tighten connector. (Keep actuator cap for
recharge and maintenance procedures.)
REMOVE
ACTUATOR CAP
AND KEEP
PLACE SYSTEM
IN ISOLATE
MODE
009350
WRITE INSTALL DATE
ON PAD LABEL
MAKE SURE
MANUFACTURING DATE
IS READABLE
009169
009170
VERIFY O-RING
ON PAD
PAD FIELD INSTALLED IN CABLE
009171
CAUTION
FOR ELECTRIC ACTUATION
ONLY 1/4 IN. BRASS PLUGS
MUST REMAIN IN PLACE OR
FIRE SUPPRESSION SYSTEM
WILL NOT OPERATE.