SECTION 10 – APPENDIX
PAGE 10-4 REV. 0 2014-MAY-02
CHEMICAL RESISTANT CHART
(For Linear Detector material)
This chemical resistance chart cannot predict the effect on the
outer covering to complex chemical mixtures. The appropriate
chemical resistance tests using a representative sample of the
chemical(s) or a trial installation of the Linear Detector should
be performed to determine acceptable product performance.
Maximum
Percent Temperature
Chemical
Concentration
°F (°C)
Acids
Hydrochloric
37
302 (150)
Hydrofluoric
50
302 (150)
Nitric
65
151
(66)
Phosphoric
85
302 (150)
Bases
Ammonium hydroxide 30
302 (150)
Potassium hydroxide
30
250 (121)
Sodium hydroxide
50
250 (121)
Sodium hypochlorite
5 - stabilized
302 (150)
at pH 12
Hydrocarbons
n-Hexane
100
302 (150)
Toluene
100
151
(66)
Alcohols and Ethers
Methanol
100
149
(65)
Ethanol
100
57
(14)
Organic Acids, Esters and ketones
Acetic acid
100
>221 (>100)
50
>250 (>121)
Acetone
100
151
(66)
Acetophenone
100
122
(50)
Ethyl Acetate
100
122
(50)
Maximum
Percent Temperature
Chemical
Concentration
°F (°C)
Classic Polymer Solvents
Dimethyl formamide
100
122
(50)
Dimethyl sulphoxide
100
212 (>100)
N-Methylpryrrolidone
100
77
(25)
Halogenated Solvents
Chlorobenzene
100
151 (66)
Cholroform
100
Not resistant
Amines and Nitriles
Acetonitrile
100
>212 (>100)
Aniline
100
212 (100)
Dimethyl amine
100
77
(25)
Peroxides
Hydrogen peroxide
30
>190
(>88)
Automotive Fluids
Crude Oils
100
302
(150)
Dexron II (gear oil)
100
302
(150)
Gasoline
100
302 (150)
Diesel Fuels
100
302
(150)
Mineral Oil
100
302
(150)
CHECKFIRE 210
Detection and Actuation System