III-31
(3) MODBUS Specification
Detail specification of MODBUS is per table 1.
Transmit mode is supported RTU mode only. TXT mode is not supported.
Table 1; MODBUS Specification
Parameters Specification Default
Operation
Transmit mode RTU Only
RTU
Not selectable
Baud Rate
4800 / 9600 / 19200
9600
Set by commissioning software
Parity
EVEN / ODD / NONE
EVEN
Set by commissioning software
Bit Length
8
8
Not selectable
Stop Bit
1
1
Not selectable
Slave Address
000-247
000
Set by commissioning software
Connection RS-232C
RS-232C Not
selectable
RS1 MODE
D-OUT / MODBUS
D-OUT
Set by commissioning software
Note
If you desire to maintain the IP class with digital communication, please consult manufacturer
or representative. The IP class cannot be maintained with standard LAN cables (straight type)
with standard skin-top connector.
(4) Configuration for MODBUS communication
4-1. Set protocol for MODBUS output on Digital Port 1
Change the “MODE” to MODBUS on the [UF-INPUT-RS-232C] tab as below display by
commissioning software which connected with Digital Port 2 side.
[Setting Parameters]
aa. MODE ; 1:MODBUS
bb. BAUD RATE; Adapt to MODBUS master setting
cc. PARITY ; Adapt to MODBUS master setting
4-2. Set Slave Address
You can select slave address from 000 to 247.
Summary of Contents for UFL-30
Page 1: ...Doc No KF08 001J Ultrasonic Flowmeter UFL 30 Installation Operation Manual ...
Page 11: ... 10 blank ...
Page 12: ...I Installation ...
Page 60: ...II Operation ...
Page 109: ...II 50 blank ...
Page 110: ...III Other ...
Page 123: ...III 14 III 2 5 Dimensions Main Unit ...
Page 128: ...III 19 blank ...
Page 129: ...III 20 blank ...
Page 145: ...III 36 blank ...
Page 165: ...III 56 blank ...