III-9
Measurement
display
(cont.)
Display content
Warnings
Backup battery remaining life
- “B” displayed when battery voltage falls below prescribed value.
Not detectable when battery would not be equipped itself.
No Echo received warning
- “R” displayed during processing when no wave received.
Disturbance Detection
- “D” displayed when the measuring condition disturbed by air bubbles, solids
or other factors.
Over Range
- "O" displayed when the measuring value exceeds upper or lower limitation
setting.
Check
“<A-->”, “<-R->”, “<--M>” displayed during various check
operations.
(A: 4-20 check: R: range check; M: multi-path check)
“<ARM>” appears during combined display.
Totalizing
Status
"I" displayed blinking when totalizing function operated.
Failure warning “ERR01” to “ERR63” displayed during equipment failure.
Check operation display is replaced by this failure display.
Status 1
“AGC” displayed in case of AGC function on.
“LO-RNG” displayed in case of low range output.
"HI-RNG" displayed in case of high range output.
Status 2
Number of “R-OFF warning” function worked.
Number of “Disturbance Elimination” function worked.