II-44
g. AGC
function
The Automatic Gain Control function controls the gain automatically to maintain the reception
echo at the level set with AGA when the reception echo becomes unstable.
Normally the Auto Gain Control is kept off, that is, [0: OFF] under CHK-6: AGC.
Note:
The AGC function must not be used in cases of turbulent flow as disturbances (air bubbles,
cavitation, etc.) may hamper the flowmeter ‘s ability to regain proper measurement function.
AGC should not be activated especially when there is a flow control valve located close
upstream due to the possibility of cavitation occurring.