2-a-9 Transducer Setting
Fasten the belts and check to insure that the mounting rail position is parallel to the pipe axis and
then firmly tightening the belts.
After the mounting rail is fixed in such manner, set the transducers into the holders in the fixture.
The transducers should be positioned on the sanded area of the pipe and the distance between
the center marks of the two transducers should be the determined F-dist.
Confirm correctness of all conditions and tightly fasten the screws on the fixture plates and secure
the transducers. Replace the fixture cover with screws.
[ Reference ]
For Z-method installation refer to "1-B. Direct Transmission Method (Z-method)".
For Multi-channel installation refer to "1-C. Multi-Path Transducer Installation".
Note: Transducer cables should be outward each other.
F-Dist
Transducer mark
Transducer holder
Transducer
Fig.1-2-9-30
View of Transducer Setting Prior to Mounting Plate Installation
Worm screw belt
Mounting fixture and transducer
Extension belt
Pipe
Fig.1-2-9-31
View of Completed Installation of Transducers for Small Dia. Pipe
I- 35