22
••••
3 - 505 SoftShop Basics
5.
To set up shared documentation, click the Advanced button on the
Open Program dialog box.
Result: The Share Address Documentation dialog box appears.
6.
Enter the share address documentation program name in the Shared
File and Path line or select Browse to locate an existing file.
7.
Click Next and enter the refresh rate (time lag between updates from
other users of the database). Valid times are from 1 to 1440 minutes.
8.
Click Next and Finish.
9.
In the Program Type area, select Offline or Connect to PLC. If you
select Connect to PLC, you can use the previously saved
communication port or select a new communication port by clicking
the Setup button. If you select Connect to PLC, you can check other
options such as:
•
Transfer Logic to PLC. Transfers all blocks and data areas
to the PLC, and loads documentation.
NOTE
To avoid overwriting the online ladder with the version stored on
file and associating documentation with the online ladder; do not select
Transfer Logic to PLC.
•
Read All NOPs. Reads 30 consecutive NOP instructions
and assumes the end of program logic. This can
substantially increase the time to connect online to a 520,
525, 530, 535, 560, or 565 controller when selected.
NOTE
If you select Read All NOPS and have more than 30 NOP
instructions separating user logic, all logic past the 30 NOPS will not be
read.
10.
Click OK or press Enter to open your program.
NOTE
If your controller is a 575, refer to
Connecting Online to a 575
in
this chapter for information on selecting Application ID and configuring
ports.
Address/Network Mode
11.
If there is no file transferred online when the program first opens
then the ladder rungs are referenced in the old TISOFT Address
Mode. When the complete program has been load the program
can be converted over to network mode. To accomplished this
select Switch to Network Display from the Options Menu. The
rungs are now displayed in Network and Address Mode. Once
rungs have been converted Network/Address mode they cannot
be converted back to Address Mode only.
Loading Parts of an Existing Logic Program Online
505 SoftShop allows you to load parts of an existing logic file to an
online 505 controller. One or more of the following parts can be loaded:
•
Ladder
•
Special Function Programs
•
Special Function Subroutines