Simatic 505 SoftShop
6 - Programming
••••
129
Caution
If you execute Power Up Restart with the controller battery
switch set to Off, all programs residing in the controller will be
cleared. Be certain to check battery switch position before using
Power Up Restart.
To execute
Power Up Restart:
1.
Click
Power Up Restart
from the PLC Operations dialog box.
2.
When you receive the message,
Execute
a
PLC power up
restart?
Select either YES or NO.
3.
For 575 controllers, you are also prompted with
Coordinate
Reset With Other Applications:
and
Coordinate Reset With
Entire System:
For each of these prompts, press NO or YES as
required for your process.
Partial Restart
Use a Partial Restart to clear all discrete elements except retentive C and
forced elements. The word elements and presets are not reset.
To execute a
Partial
Power Up Restart:
1.
Click
Partial Restart
from the PLC Operations dialog box.
2.
When you receive the message,
Execute
a
Partial restart?
Select either YES or NO.
3.
For 575 controllers, you are also prompted with
Coordinate
Reset With Other Applications:
and
Coordinate Reset With
Entire SYSTEM:
For each of these prompts, press NO or YES
as required for your process.
Complete Restart
Use Complete Restart to clear all discrete elements and word elements,
including
retentive C elements. Complete Restart also clears controller
fatal errors. Forced discrete elements and forced word elements are not
reset.
To execute Complete Restart:
1.
Click
Complete Restart
from the PLC Operations dialog box.
2.
When you receive the message,
Execute
a
Complete restart?
Select either YES or NO.
For 575 controllers, you are also prompted with
Coordinate Reset With
Other Applications:
and
Coordinate Reset With Entire System:
For
each of these prompts, press NO or YES as required for your process.