054
4.1 Function Code
F7 Group - Digital Input and Output Parameters
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default Modification
F7.25 FDT1 level
0.00Hz ~【F0.16】upper limit
freq.
0.01Hz 50.00
○
F7.26 FDT1 lag
0.0 ~ 100.0% *【F7.25】
0.1%
2.0%
○
F7.27 FDT2 detection
method
0: speed set value
1: speed detected value
1
0
○
F7.28 FDT2 level
0.00Hz ~【F0.16】upper limit freq.
0.01Hz 25.00
○
F7.29 FDT2 lag
0.0 ~ 100.0% *【F7.28】
0.1%
4.0%
○
F7.30 Counting value arrival
processing
0: stop counting, stop output
1: stop counting, resume output
2: cycle count, stop output
3: cycle count, resume output
1
3
×
F7.31 Counting start
condition
0: always count since power on
1: count in operation status, stop
counting in stop status
1
1
×
F7.32 Counter reset value 【F7.33】~ 65535
1
0
○
F7.33 Counter detection
value
0 ~【F7.32】
1
0
○
F7.34 time out processing
0: stop timing, stop output
1: stop timing, resume output
2: cycle timing, stop output
3: cycle timing, resume output
1
3
×
F7.35 Timing start condition
0: timing starts since power on
1: timing starts in operation status,
and stops in stop status
1
1
×
F7.36 Timing setting
0 ~ 65535s
1s
0
○
F7.37 Y1 turn off delay time 0.0 ~ 100.0s
0.1s
0.0
×
F7.38 Y2 turn off delay time 0.0 ~ 100.0s
0.1s
0.0
×
F7.39 R1 turn off delay time 0.0 ~ 100.0s
0.1s
0.0
×
F7.40 R2 turn off delay time 0.0 ~ 100.0s
0.1s
0.0
×