077
F0.07
Main freq. source A
0 ~ 10
0
0: digital set 1( , encoder)
The frequency is originally set as F0.12, but
can be adjust with key or encoder.
The modified frequency value will be saved
to F0.12 after power down (if no need for
saving, set the F0.10 as 1).
1: digital set 2 (up/down terminal adjust)
The initial value of frequency is F0. 13. The
running frequency can be changed by on/
off of multi-functional terminal defined
as UP/DOWN (for details check F7 group
function code of X terminal increase/
decrease item). When UP and COM terminal
are both closed, frequency increase; when
DOWN and COM terminal are both closed,
frequency decrease; when UP/COM terminal
and COM terminal are both open or closed
at the same time, the frequency remains
unchanged. If set frequency saving upon
power down, the modified frequency value
will be saved to F0.13 after power down.
The modifying rate of running frequency by
UP/DOWN terminal can be set by function
code F7.12.
▲ / ▼
▲ / ▼
Note:
No matter set by key or terminal UP/
DOWN, the set value is added with a regulating
variable based on F0.12 or F0.13, and the final output
frequency ranges from the lower limit to the maximum
output value. The regulating variable via terminal UP/
DOWN can be cleared by choosing "UP/DOWN
terminal frequency zero clearing" via X terminal, and
the regulating variable of keypad can be cleared by
choosing "clear key set of frequency" via key
.
▲ / ▼
▲ / ▼
M-FUNC
F0.06
Operation command channel
0 ~ 2
0
This function code is used for choosing the
physical channel for receiving operation
commands like run and stop.
0: keypad run command channel
Controlled with keys in keypad like ,
, .
1: terminal run command channel
Controlled by muli-function terminals
defined as FWD, REV, JOG forward, JOG
reverse.
2: communication run command channel
Controlled with communication method via
upper computer.
RUN
M-FUNC
STOP/RESET
Note:
Even during running status, the run
command channel can be changed by
modifying this function code set value.
Please set carefully!
Note: factory default is 0 for above 55KW, and 1 for
under 55KW.
output. But considering its sensitivity to
motor parameter, the operator had better
activate the dynamic self-learning of motor
parameters for a better effect.
3: reserved
4: separation type V/F control
With this control mode, the output voltage
and frequency of VFD can both be controlled
individually, not according a constant V/F
relation. It can be used in areas like variable-
frequency power source and EPS.
4.2 Detailed Function Description