106
F0.09 (frequency combinational algorithm)
is set as 7, the frequency setting channel is
switched to frequency source (A+K*B), and
back to A if it is disabled.
31: switch from frequency source A to A-K*B
When this terminal function is enabled, if
F0.09 (frequency combinational algorithm)
is set as 8, the frequency setting channel is
switched to frequency source (A-K*B), and
back to A if it is disabled.
32: reserved
33: PID control input
This terminal function is enabled when
frequency is input via PID manually. Refer
to F8 group parameter setting for details.
34: PID control pause
This terminal function is used for pause
control of operating PID. When it is
enabled, PID adjustment will stop and
the VFD remain the present frequency.
Continue PID adjustment when the
function is disabled, the running frequency
will change to the adjustment.
35: start traverse operation
If the traverse operation is set to be manual
start, then traverse function is enabled if
this function is selected. Otherwise the
VFD runs with preset frequency of traverse
operation. Refer to F9.55 ~ F9.65.
36: pause traverse operation
Short-circuit the terminal with COM,
the VFD will stop the traverse operation
and remain the present frequency; if the
terminal is disabled, the VFD will resume
traverse operation.
37: traverse reset
If this function is selected, closing the
terminal can clear the information about
traverse status no matter the drive is
in auto or manual start mode. Traverse
operation continues after this terminal is
disconnected (run preset freq. if there is
preset freq.). See F9.55 ~ F9.65.
38: PLC control input
This terminal function is enabled when
PLC input method is manual input
method via multi-function terminal, and
PLC operates normally when operating
command arrives; if the terminal function
is disabled, the VFD runs in zero frequency
when operating command arrives.
39: PLC pause
It is used to pause the PLC operation. The
driver will operate at zero frequency if
this terminal is enabled, but the running
time is not counted; if the terminal is
disabled, the driver will start in rotating
speed tracking method and continue the
PLC operation. Refer to F9.00 ~ F9.53 for
function description.
40: PLC status reset
When the drive stops in PLC mode and
this terminal function is enabled, the
memorized PLC operating information
(operating stage, operating time, operating
frequency, etc.) will be cleared. The driver
will restart if the terminal function is
disabled. See F9.
41: clear the counter to zero
Short-circuit the terminal with COM, this
function is to clear to zero and is used in
conjunction with function NO.42.
42: input signal to trigger the counter
This terminal is used to input counting
pulse signal to the internal counter of the
4.2 Detailed Function Description