033
4.1 Function Code
F0 Group - Basic Run Parameters
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default
Modification
F0.18 Frequency output
mode
0: low frequency mode
(0.00 ~ 300.00Hz)
1: high frequency mode
(0.0 ~ 3000.0Hz)
Note: high frequency mode is
only effective to VF control
1
0
×
F0.19 Acceleration time 1
0.1 ~ 3600.0s
0.4 ~ 4.0KW 7.5s
5.5 ~ 30.0KW 15.0s
37.0 ~ 132.0KW 30.0s
160.0 ~ 630.0KW 60.0s
0.1s
Depending
on model
○
F0.20 Deceleration tima 1
0.1s
Depending
on model
○
F0.21 Running direction
0: forward
1: reverse
2: prevent reversing
1
0
×
F0.22 Carrier frequency
1.0 ~ 16.0KHz
0.4 ~ 4.0KW 6.0KHz
1.0 ~ 16.0KHz
5.5 ~ 30KW 4.0KHz
1.0 ~ 16.0KHz
37 ~ 132KW 2.5KHz
1.0 ~ 10.0KHz
160 ~ 630KW 1.5KHz
1.0 ~ 5.0KHz
0.1KHz Depending
on model
○
F0.23 User password
1: 0 ~ 9: no password
protection
2: The password setting is
successful and will take 3
minutes to take effect
3: Write protection is not
valid for this parameter and
cannot be initialized
1
0
○
Summary of Contents for SKI600
Page 3: ......
Page 4: ...88888 Operating Instruction Manual High performance Vector Inverter ...
Page 179: ......
Page 180: ......