078
F0.08
Auxiliary freq. source B
0 ~ 9 (principle freq.
channel selection)
3
0: digital set 1 (keypad , encoder)
1: digital set 2
(UP/DOWN terminal adjustment)
2: digital set 3 (communication setting)
3: AI1 analog set (0 ~ 10V/20mA)
4: AI2 analog set (0 ~ 10V)
5: impulse set (0 ~ 50KHZ)
6: simple PLC setting
7: multispeed running setting
8: PID control setting
9: panel potentiometer setting
Auxiliary frequency specified channel has
the same meaning of each item as principle
frequency channel, for details check F0.07
description.
▲ / ▼
2: digital set 3 (communication set)
Modify the set frequency via serial port
frequency set command, for details check
FB group communication parameter.
3: AI1 analog set (0 ~ 10V/20mA)
The frequency setting is determined by
analog voltage/current of AI1 terminal,
and the input range DC 0 ~ 10V/20mA. The
relevant setting is in F6.00 ~ F6.05.
4: AI2 analog set (0 ~ 10V)
Frequency setting is determined by analog
voltage/current of AI2 terminal, input
ranges DC 0 ~ 10V. The relevant setting is in
F6.06 ~ F6.11.
5: impulse set
Frequency setting is determine by terminal
impulse frequency (only input via X7, see
F7.06). Input impulse signal specification:
high level range 15 ~ 30V; frequency
range 0 ~ 50kHz. The relevant setting is in
F6.15 ~ F6.20.
6: simple PLC set
It needs to set function code F9.00 ~ F9.05
to select this mode. Function code
F9.00 ~ F9.21 are used to determine the
running frequency of each PLC section, and
F9.22 ~ F9.53 are used to the increase/
decrease time and running time of each
section.
7: multispeed running setting
The VFD runs in multispeed mode in this
frequency setting mode. Set the F7 group
"X terminal as multispeed" and F9 group
"multispeed fiequency" function code to
determine the correspondence of specified
section number and frequency.
8: PID control setting
The VFD runs in process PID control mode in
this frequency setting mode. Function codes
of F8 group are needed to be set such as
"process PID parameter", analog given and
impulse given. The running frequency of
VFD is the value after PID taking effect. For
details check F8 group function description.
9: panel potentiometer setting
Operate the potentiometer on keyboard to
adjust running frequency, and regulating
range is 0 ~ max. output frequency【F0.15】.
4.2 Detailed Function Description