159
5.9 Communication Address of all Parameters:
Notice:
◇
In the above examples, the driver address is 01, which makes it better for illustration; when
the driver is slave, the address setting range is 1 ~ 247, and if any data of frame format is
changed, the check code needs to be recalculated. The calculating tools of 16bit CRC check
code can be download from internet.
◇
Initial address of monitor item is D000, each item offset corresponding hexadecimal value
based on this address, then plus it with the initial address. For example: the monitor initial
item is d-00, the corresponding initial address is D000H (1D00H), now read monitor item
d-18, 18-00=18, the corresponding hexadecimal of 18 is 12H, then the read address of d-18 is
D000H+12H = D012H (1D00H+12H = 1D12H). Address D000H and 1D00H are interchangeable.
◇
Frame format when the slave response information is abnormal: driver a
(80H+function code) + 16bit CRC check code; if the salve return frame is 01H + 83H + 04H +
40F3H, then 01H is slave address, 83H is 80H+03H indicating read error, 04H is invalid data
length, 40F3H is 16bit CRC check code.
Function code
Communication address
F0.00 ~ F0.22
0000H ~ 0016H
F1.00 ~ F1.37
0100H ~ 0125H
F2.00 ~ F2.17
0200H ~ 0211H
F3.00 ~ F3.08
0300H ~ 0308H
F4.00 ~ F4.27
0400H ~ 041BH
F5.00 ~ F5.24
0500H ~ 0518H
F6.00 ~ F6.52
0600H ~ 0634H
F7.00 ~ F7.36
0700H ~ 0724H
F8.00 ~ F8.33
0800H ~ 0821H
F9.00 ~ F9.73
0900H ~ 0949H
FA.00 ~ FA.35
0A00H ~ 0A23H
FB.00 ~ FB.07
0B00H ~ 0B07H
FC.00 ~ FC.28
0C00H ~ 0C1CH
FE.00 ~ FE.15
0E00H ~ 0E0FH
FF.00 ~ FF.22
0F00H ~ 0F16H
d-00 ~ d-57
D000H(1D00H)~ D039H(1D39H)
Communication Protocol