133
100: no times limit, i.e. infinite times
When fault occurs during operation, the driver
will stop output and display fault codes. After
a period of time specified by FC.07, the driver
will auto reset and restart according to set
start mode.
The auto reset times after fault occurring is
specified by FC.06. When it is set at 0, auto
restart function will be disabled and the driver
can only be reset manually. When FC.06 is set
at 100, there will be no limit for reset times.
For IPM fault, external fault, etc., auto reset
function of the driver is not allowed.
FC.06
Auto reset times
0 ~ 100
0
FC.07
Auto reset interval
0.1 ~ 6000m
3.0
Notice
◇
FA.02 needs to be set at 0 to ensure the
restart after power off is valid.
◇
this parameter may cause unexpected
start of motor and bring damage to
equipment and people, be cautious to
use it.
4.2 Detailed Function Description
FC.08
Cooling fan control
0 ~ 1
0
0: auto control mode
1: operation all the way during power on
FC.09
Password of operation limit function
0 ~ 65535
0
By default, the password is 0, and FC.10 and
FC.11 can be set; when there is a password,
the setting of FC.10 and FC.11 should be after
the password is verified right.
The password can be set at 0 if there is no
need for it.
For this password setting, input five-digit
number and press , the password
will take into effect after one minute later.
When there is a need to modify the password,
choose FC.09 function code, press to
enter verification status. After successful
authentication, enter modify status and
input the new password, press , and
the password is modified successfully. One
minute later, the new password will take into
effect automatically. For clear password, just
set it at "00000".
ENTER
ENTER
ENTER
FC.10
Operation limit function
0 ~ 1
0
0: disabled
1: enabled
During operation limit, as long as the total
operation time exceeds the time specified
by FC.11, the driver will respond with
protection action and coast to stop, and the
keypad displays E-26 (RUNLT). To clear this
fault, just very FC.09 right and set FC.10 at
"0"(disabled).