074
4.1 Function Code
FF Group - Factory Parameter
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default Modification
FF.00 Factory Password
0 ~ 65535
Note: After password setup was
successful, it will take 3 minutes
to take effect
1
0
○
FF.01 Reserved
—
—
0
◇
FF.02 VFD Model
0 ~ 30
0: 0.4KW 1: 0.75KW 2: 1.5KW
3: 2.2KW 4: 4.0KW 5: 5.5KW
6: 7.5KW 7: 11KW 8: 15KW
9: 18.5KW 10: 22KW 11: 30KW
12: 37KW 13: 45KW 14: 55KW
15: 75KW 16: 90KW 17: 110KW
18: 132KW 19: 160KW 20: 185KW
21: 200KW 22: 220KW 23: 250KW
24: 280KW 25: 315KW 26: 350KW
27: 375KW 28: 400KW 29: 500KW
30: 630KW
1
Model
Dependant
◇
FF.03 Rated Power
0.4 ~ 999.9KW
Note: this parameter can only be
viewed
0.1KW
Model
Dependant
◇
FF.04 Rated Voltage
0 ~ 999V
1V
380
◇
FF.05 Rated Current
0.1 ~ 6553.5A
0.1A
Model
Dependant
◇
FF.06 Dead Zone Time
3.2 ~ 10.0μS
0.4 ~ 4.0KW 3.2μS
5.5 ~ 22KW 3.5μS
30 ~ 110KW 4.0μS
132 ~ 630KW 4.5μS
0.1μS
Model
Dependant
◇
FF.07 Software
Overvoltage Point
220V:0 ~ 450V 400V
380V:0 ~ 850V 800V
1V
Model
Dependant
◇
FF.08 Software
Undervoltage Point
220V:0 ~ 280V 150V
380V:0 ~ 320V 250V
1V
Model
Dependant
◇
FF.09 Software
Overcurrent Point
50.0 ~ 250.0%
0.1%
220.0%
◇
FF.10 Voltage Correction
Factor
80.0 ~ 120.0%
0.1%
100.0%
◇
FF.11 Current Correction
Factor
50.0 ~ 150.0%
0.1%
100.0%
◇