4.2 Detailed Function Description
F0.04
VFD type
0 ~ 1
0
0: G type (constant torque load type)
1: P type (fan and water pump load type)
For our VFD products, G/P type are
combined, i.e. G type inverter can be used
as P type inverter with power of one grade
higher, but only if the function code is set
with corresponding value.
0: common V/F control
This control mode is used when there is
a need to drive one more motors with a
single inverter and there is no access to
the parameters of controlled motor. This
control mode is most commonly used and
applied in any circumstance where no strict
requirement is needed for the motor control
performance.
1: advanced V/F control
This control mode introduced flux closed
loop control idea, and achieved a large
improvement of torque response of motor
control in full frequency range, torque
output ability in low frequency, without
the sensitivity to motor parameter as field-
oriented vector control. It is especially
suitable to situation where there is certain
requirements for starting torque (like
drawbench, ball mill, etc.).
2: open loop current vector control (sensitive
to motor parameter)
As a real current vector control mode, it
has both high torque output performance
as flux control mode and flexible torque
F0.05
Control mode
0 ~ 4
Depending on model
The above function codes are used for
indicating the relevant information of VFD,
which can not be modified but only checked
F0.01
Control software version
1.00 ~ 99.99
1.02
F0.02
Keypad software version
1.00 ~ 99.99
1.00
F0.03
VFD rated power
0.4 ~ 999.9KW(G/P) Depending
on model
F0 system management parameter
Note:
Please keep the password carefully, and seek help from
the manufacture once lost the password.
F0.00
/
/
/
User password setting function could prevent
unauthorized person from checking and
modifying the function parameters.
To avoid misoperation, user password less
than 10 is invalid.
When setting the user password, input a
number not less than 10, press to
confirm, and the password will take into effect
after one minute.
To modify the password, choose F0.00
function code, and press to enter
password authentification status. After the
authentification is successfully done, enter
modifying status and input a new password,
press to confirm, and the modifying
will be done successfully. New password will
take into effect after 3 minutes.
ENTER
ENTER
ENTER