4.1 Function Code
FA Group - Protective Parameters
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default Modification
FA.12 Overload pre-alarm
level
G type: 20%~ 200% *VFD rated
current 160%
P type: 20%~ 200% *VFD rated
current 120%
1%
Depending
on model
○
FA.13 Overload pre-alarm
delay time
0.0 ~ 300s
0.1s
10.0
○
FA.14 Temperature
detection threshold 0.0℃~ 90.0℃
0.1℃
65.0℃
×
FA.15
Phase loss
protection of input
and output
0: disabled
1: disabled for input, enabled for
output
2: enabled for input, disabled for
output
3: enabled
1
Depending
on model
×
FA.16 Delay time of input
phase loss protection 0.0 ~ 30.0s
0.1S
1.0
○
FA.17
Detection reference
of output phase loss
protection
0%~ 100% *VFD rated current
1%
50%
×
FA.18
Detection factor
of output current
imbalance
1.00 ~ 10.00 1.00: imbalance
detection is disabled
Note: detection of output
current imbalance and output
phase loss share the same
reference parameter FA.17 and
fault code E-13.
—
1.00
×
FA.19 reserved
—
—
0
◆
FA.20
PID feedback
disconnection
processing
0: disabled
1: alarm and maintain the
operation at the frequency of
disconnection moment
2: protection action and coast to stop
3: alarm and decelerate to zero-
speed operation according to
preset mode
1
0
×