030
4.1 Function Code
F0 Group - Basic Run Parameters
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default
Modification
F0.05 Control mode
0: common V/F control (manually
torque boost)
1: advanced V/F control
(automatically torque boost)
2: open loop current vector control
(SVC)
3: closed loop current vector control
(rserved)
4: separatd type V/F control
Note 1: choose control method 3
(closed loop current vector control),
input terminal X6 can only be used for
ordinary terminal, not for high-speed
pulse input.
Note 2: this parameter can not be
initialized, please modify it manually.
1
Depending
on model
×
F0.06
operation
command
channel
0: operation panel run command
channel
1: terminal run command channel
2: communication run command
channel
1
0
○
F0.07
Main
frequency
source A
0: digital set 1 (keypad ▲ / ▼ key,
F0.12)
1: digital set 2 (terminal UP/DOWN
F0.13)
2: digital set 3 (communication set)
3: AI1 analog set (0 ~ 10V/20mA)
4: AI2 analog set (0 ~ 10V)
5: pulse set (0 ~ 50KHZ)
6: easy PLC set
7: multistage speed run set
8: PID control set
9: panel Potentiometer
10: MPPT turn on
1
0
○