Instruction Manual
IM-106-880, Rev 2.1
April 2017
OCX 8800
7-36
Table 7-26. PID Function Block System Parameters
Parameter
Index
Number
Units
Description
ACK_OPTION
46
None
Used to set auto acknowledgment of alarms.
ALARM_HYS
47
Percent
The amount the alarm value must return to within the alarm limit before the
associated active alarm condition clears.
ALARM_SUM
45
None
The summary alarm is used for all process alarms in the block. The cause of
the alert is entered in the subcode field. The first alert to become active will
set the Active status in the Status parameter. As soon as the Unreported sta-
tus is cleared by the alert reporting task, another block alert may be reported
without clearing the Active status, if the subcode has changed.
ALERT_KEY
04
None
The identification number of the plant unit. This information may be used in
the host for sorting alarms, etc.
ALG_TYPE
74
None
Selects filtering algorithm as Backward or Bilinear.
BAL_TIME
25
Seconds
The specified time for the internal working value of bias to return to the oper-
ator set bias. Also used to specify the time constant at which the integral term
will move to obtain balance when the output is limited and the mode is AU-
TO, CAS, or RCAS.
BIAS
66
EU of OUT_SCALE
The bias value used to calculate output for a PD type controller.
BKCAL_HYS
30
Percent
The amount the output value must change away from the its output limit be-
fore limit status is turned off.
BKCAL_IN
27
EU of OUT_SCALE
The analog input value and status from another block’s BKCAL_OUT output
that is used for backward output tracking for bumpless transfer and to pass
limit status.
BKCAL_OUT
31
EU of PV_SCALE
The value and status required by the BKCAL_IN input of another block to
prevent reset windup and to provide bumpless transfer of closed loop control.
BLOCK_ALM
44
None
The block alarm is used for all configuration, hardware, connection failure, or
system problems in the block. The cause of the alert is entered in the sub-
code field. The first alert to become active will set the active status in the sta-
tus parameter. As soon as the Unreported status is cleared by the alert
reporting task, and other block alert may be reported without clearing the Ac-
tive status, if the subcode has changed.
BLOCK_ERR
06
None
This parameter reflects the error status associated with the hardware or soft-
ware components associated with a block. It is a bit string so that multiple er-
rors may be shown.
BYPASS
17
None
Used to override the calculation of the block. When enabled, the SP is sent
directly to the output.
CAS_IN
18
EU of PV_SCALE
The remote setpoint value from another block.
CONTROL_OPTS
13
None
Allows you to specify control strategy options. The supported control options
for the PID block are Track enable, Track in Manual, SP-PV Track in Man,
SP-PV Track in LO or IMAN, Use PV for BKCAL OUT, and Direct Acting.
CONTROL_OPTS
13
None
Allows you to specify control strategy options. The supported control options
for the PID block are Track enable, Track in Manual, SP-PV Track in Man,
SP-PV Track in LO or IMAN, Use PV for BKCAL OUT, and Direct Acting.
DV_HI_ALM
64
None
The DV HI alarm data, which includes a value of the alarm, a timestamp of
occurrence, and the state of the alarm.
DV_HI_LIM
57
EU of PV_SCALE
The setting for the alarm limit used to detect the deviation high alarm condi-
tion.
DV_HI_PRI
56
None
The priority of the deviation high alarm.
DV_LO_ALM
65
None
The DV LO alarm data, which includes a value of the alarm, a timestamp of
occurrence, and the state of the alarm.
DV_LO_LIM
59
EU of PV_SCALE
The setting for the alarm limit use to detect the deviation low alarm condition.
DV_LO_PRI
58
None
The priority of the deviation low alarm.
ERROR
67
EU of PV_SCALE
The error (SP-PV) used to determine the control action.
FF_ENABLE
70
None
Enables the use of feedforward calculations.
Summary of Contents for OCX 8800
Page 2: ......
Page 4: ......
Page 10: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 ii ...
Page 72: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 4 8 ...
Page 88: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 5 16 ...
Page 100: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 6 12 ...
Page 164: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 7 64 ...
Page 176: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 8 12 ...
Page 213: ......
Page 223: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 10 11 ...
Page 225: ......
Page 262: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 C 2 ...