Instruction Manual
IM-106-880, Rev 2.1
April 2017
OCX 8800
7-33
AI
Function
Block
OUT_D
PID
Function
Block
AO
Function
Block
OUT
IN
Differential Pressure Transmitter to Measure Flow
Situation
The liquid flow in a line is to be measured using the differential pressure
across an orifice plate in the line, and the flow measurement will be used
in a flow control loop. Based on the orifice specification sheet, the
differential pressure transmitter was calibrated for 0 to 20 in H
2
0 for a flow
of 0 to 800 gal/min, and the transducer was not configured to take the
square root of the differential pressure.
Solution
Table 7-24 lists the appropriate configuration settings, and Figure 7-12
illustrates the correct function block configuration.
Table 7-24. Analog Input
Function Block Configuration for
a Differential Pressure
Measurement
L_TYPE
Indirect Square Root
XD_SCALE
0 to 20 in.
OUT_SCALE
0 to 800 gal/min
Figure 7-12. Function Block Diagram for a Differential Pressure Transmitter Used in a Flow Measurement
Analog
Measurement
BKCAL_INBKCAL_OUT
Parameter
Configured Values
3
8
7
4
0
0
8
9
Summary of Contents for OCX 8800
Page 2: ......
Page 4: ......
Page 10: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 ii ...
Page 72: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 4 8 ...
Page 88: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 5 16 ...
Page 100: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 6 12 ...
Page 164: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 7 64 ...
Page 176: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 8 12 ...
Page 213: ......
Page 223: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 10 11 ...
Page 225: ......
Page 262: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 C 2 ...