PM1RM ROUND CAMLOCK™
Recessed junction box installation
REVISION DATE
7-27-09
REFERENCE NUMBER
INS-1515A
40429 Brickyard Drive • Madera, CA 93636 • USA
559.438.5800 • FAX 559.438.5900
www.bklighting.com • [email protected]
B - K L I G H T I N G
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF B-K LIGHTING, INC. AND ITS RECEIPT OR POSSESSION DOES NOT CONVEY ANY RIGHTS TO REPRODUCE, DISCLOSE ITS CONTENTS, OR TO MANUFACTURE, USE OR SELL ANYTHING IT MAY DESCRIBE.
REPRODUCTION, DISCLOSURE OR USE WITHOUT SPECIFIC WRITTEN AUTHORIZATION OF B-K LIGHTING, INC. IS STRICTLY FORBIDDEN.
•
Product must be installed by a qualified person in a manner
consistent with its intended use and in compliance with the
National Electrical Code, Canadian Electrical Code, and all Local
and Provincial Codes.
•
Follow product label information and instructions.
•
Qualified Personnel must perform all servicing or relamping of
this product.
•
Before wiring to power supply and during servicing or
relamping, turn off power at fuse or circuit breaker before
service.
IMPORTANT SAFETY INFORMATION - READ, FOLLOW, AND SAVE ALL SAFETY AND INSTALLATION INSTRUCTIONS
•
The use of accessory equipment not recommended by the
manufacturer or installed contrary to instructions may cause an
unsafe condition. The use of damaged components may cause
an unsafe condition and void product warranty.
•
Do not block light emanating from product in whole or part, as
this may cause an unsafe condition.
•
Never operate the fixture with missing or damaged lens. Lens
must be cleaned on regular basis.
•
Energized lamp gets hot very quickly. Allow it to cool before
service.
•
Entire fixture may become extremely hot. Do not touch hot
lens or fixture body. Do not touch the lamp at any time. Use a
clean, dry, soft cloth to handle the lamp. Oil from skin may
damage the lamp and cause it to rupture.
•
Replace lamp only with correct wattage and type of lamp
marked on fixture label.
•
All gaskets, o-rings and sealing surfaces must be kept clean
during installation and service; failure to do this may cause an
unsafe condition and void product warranty.
1/8”, 5/64” & 9/64” allen wrench
Wire connectors
Phillips screwdriver
Level
1.
Install standard 4” octagonal/round recessed
junction box in the final fixture location
according to designed lighting plan.
2.
Pull branch circuit wiring necessary for
installation (By Others.)
Horizontal
Vertical
Round UPM mounting plate with CamLock™ assembly
UPM faceplate
UPM housing with loose transformer
Universal mounting ring
Patented 1/2” NPT knockouts*
* UPM is covered in whole or in part by US patent #6,940,012
NEEDED
FOR
INSTALLATION:
By Others
Warning
High Voltage
Hot Surface
3.
Install universal mounting ring.
IMPORTANT!! Orientation of universal ring will affect orientation of UPM! Take note of
mounting plate holes (indicated with arrows) on the universal ring holes to mount UPM in
correct orientation.