Instruction Manual
IM-106-880, Rev 2.1
April 2017
OCX 8800
7-6
OCX FUNCTION
BLOCKS
Implemented Function Blocks
Shows the OCX Implemented Function Blocks.
Table 7-1. OCX Implemented
Function Blocks
Resource Block
Transducer Block
Analog Input Block 1 (AI1)
See TB Channel Assignment Table 7-16
Analog Input Block 2 (AI2)
See TB Channel Assignment Table 7-16
Analog Input Block 3 (AI3)
See TB Channel Assigbment Table 7-16
Analog Input Block 4 (AI4)
See TB Channel Assignment Table 7-16
PID Block (PID)
Proportional/Integral/Derivative of any AI-BLOCK
Arithmetic Block (ARTHM)
Arihmetic Function Block
Input Selector Block (ISEL)
Input Selector Function Block
RESOURCE BLOCK
PlantWeb Alerts
The PlantWeb Alerts (PWA) software supports three groups of alarms for
three severity levels: 1) Failed, 2) Maintenance, and 3) Advisory. Each PWA
can be configured for one or more of the three alarm groups. The PWA alarms
and their severity level default settings are listed in Table 7-2.
Table 7-2. OCX 8800 PWA
PlantWeb Alert
Severity Level Default
Reserved: none
Sensor Malfunction
Failed
Sensor Degraded
Failed
Thermocouple Malfunction
Failed
Sensor Heater Malfunction
Failed
Sensor Heater Over Temperature
Failed
Sensor Heater Temperature Variance
Maintenance
Calibration Error
Maintenance
Calibration Recommended
Advisory
NV Memory Failure
Failed
NV Writes Deferred
Advisory
High Electronics Temperature
Maintenance
ADC Failure
Failed
Line Input Out of Range
Advisory
Inter Board Comm Failure
Failed
Simulate Active
Advisory
Each alarm condition can be “Enabled”, “Disabled”, or have alarm reporting
“Suppressed”. The PWA alarms must be “Enabled” to allow the corresponding
alarm condition to be detected. The PWA alarms can be “Suppressed” to
mask out failures from annunciation.
Function Block
Description
Summary of Contents for OCX 8800
Page 2: ......
Page 4: ......
Page 10: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 ii ...
Page 72: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 4 8 ...
Page 88: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 5 16 ...
Page 100: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 6 12 ...
Page 164: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 7 64 ...