Instruction Manual
IM-106-880, Rev 2.1
April 2017
OCX 8800
7-25
Parameter
Index
Number
Units
Description
MODE_BLK
05
None
The actual, target, permitted, and normal modes of the block.
Target: The mode t
o “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
OUT
08
EU of OUT_SCALE
The block output value and status.
OUT_D
37
None
Discrete output to indicate a selected alarm condition.
OUT_SCALE
11
None
The high and low scale values, engineering units code, and number of digits
to the right of the decimal point associated with OUT.
PV
07
EU of XD_SCALE
The process variable used in block execution.
PV_FTIME
18
Seconds
The time constant of the first-order PV filter. It is the time required for a 63%
change in the IN value.
SIMULATE
09
None
A group of data that contains the current transducer value and status, the
simulated transducer value and status, and the enable/disable bit.
STRATEGY
03
None
The strategy field can be used to identify grouping of blocks. This data is not
checked or processed by the block.
ST_REV
01
None
The revision level of the static data associated with the function block. The
revision value will be incremented each time a static parameter value in the
block is changed.
TAG_DESC
02
None
The user description of the intended application of the block.
UPDATE_EVT
20
None
This alert is generated by any change to the static data.
VAR_INDEX
39
% of OUT Range
The average absolute error between the PV and its previous mean value
over that evaluation time defined by VAR_SCAN.
VAR_SCAN
40
Seconds
The time over which the VAR_INDEX is evaluated.
XD_SCALE
10
None
The high and low scale values, engineering units code, and number of digits
to the right of the decimal point associated with the channel input value.
The XD_SCALE units code must match the units code of the measurement
channel in the transducer block. If the units do not match, the block will not
transition to MAN or AUTO.
Simulation
To support testing, you can either change the mode of the block to manual
and adjust the output value, or you can enable simulation through the
configuration tool and manually enter a value for the measurement value and
its status.
With simulation enabled, the actual measurement value has no impact on the
OUT value or the status.
Summary of Contents for OCX 8800
Page 2: ......
Page 4: ......
Page 10: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 ii ...
Page 72: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 4 8 ...
Page 88: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 5 16 ...
Page 100: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 6 12 ...
Page 164: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 7 64 ...
Page 176: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 8 12 ...
Page 213: ......
Page 223: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 10 11 ...
Page 225: ......
Page 262: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 C 2 ...