Instruction Manual
IM-106-880, Rev 2.1
April 2017
OCX 8800
7-29
Alarms are grouped into five levels of priority:
Priority Number
Priority Description
0
The priority of an alarm condition changes to 0 after the condition that
caused the alarm is corrected.
1
An alarm condition with a priority of 1 is recognized by the system, but is
not reported to the operator.
2
An alarm condition with a priority of 2 is reported to the operator, but does
not require operator attention (such as diagnostics and system alerts).
3-7
Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.
10-15
Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.
Status Handling
Normally, the status of the PV reflects the status of the measurement value,
the operating condition of the I/O card, and any active alarm condition. In Auto
mode, OUT reflects the value and status quality of the PV. In Man mode, the
OUT status constant limit is set to indicate that the value is a constant and the
OUT status is
Good.
The
Uncertain
- EU range violation status is always set, and the PV status is
set high- or low-limited if the sensor limits for conversion are exceeded.
In the STATUS_OPTS parameter, you can select from the following options to
control the status handling:
BAD if Limited
– sets the OUT status quality to Bad when the value is higher
or lower than the sensor limits.
Uncertain if Limited
– sets the OUT status quality to Uncertain when the
value is higher or lower than the sensor limits.
Uncertain if in Manual mode
– The status of the Output is set to Uncertain
when the mode is set to Manual.
NOTE
The instrument must be in
Manual
or
Out of Service
mode to set the status
option.
NOTE
The AI block only supports the
BAD if Limited
option. Unsupported options
are not grayed out; they appear on the screen in the same manner as
supported options.
Summary of Contents for OCX 8800
Page 2: ......
Page 4: ......
Page 10: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 ii ...
Page 72: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 4 8 ...
Page 88: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 5 16 ...
Page 100: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 6 12 ...
Page 164: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 7 64 ...
Page 176: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 8 12 ...
Page 213: ......
Page 223: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 10 11 ...
Page 225: ......
Page 262: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 C 2 ...