Instruction Manual
IM-106-880, Rev 2.1
April 2017
OCX 8800
7-52
Table 7-29. Arithmetic (ARTHM) Block
Index
Number
Parameter
Units
Description
4
ALERT_KEY
None
The identification number of the plant unit. This information may be used in thehost
fro sorting alarms, etc.
29
ARITH_TYPE
None
The set of 9 arithmetic functions applied as compensation to or augmentation of the
range extended input.
30
BAL_TIME
Seconds
Specifies the time for a block value to match an input, output, or calculated value or
the time for dissipation of the internal balancing bias.
31
BIAS
None
The bias value.
21
BIAS_IN_1
None
The bias value for IN_1.
23
BIAS_IN_2
None
The bias value for IN_2.
25
BIAS_IN_3
None
The bias value for IN_3.
36
BLOCK_ALM
None
This block alarm is used for all configuration, hardware, connection failure, or
system problems in the block. The cause of the alert is entered in the subcode
field.The first alert to become active will set the active status in the status parameter.
As soon as the Unreported status is cleared by the alert reporting task, and other
block alert may be reported without clearing the Active status, if the subcode has
changed.
6
BLOCK_ERR
None
The summary of active error conditions associated with the block. The possible
block errors are Block configuration error, Simulate active, Local override, Input
failure/process variable has Bad status, Output failure, Readback failed, Out of
service, and Other. Each function block reports none or a subset of these error
conditions.
27
COMP_HI_LIM
EU of PV
Determines the high limit of the compensation input.
28
COMP_LO_LI
M
EU of PV .
Determines the low limit of the compensation input.
32
GAIN
None
The proportional gain (multiplier) value.
22
GAIN_IN_1
None
The proportional gain (multiplier) value for IN_1.
24
GAIN_IN_2
None
The proportional gain (multiplier) value for IN_2.
26
GAIN_IN_3
None
The proportional gain (multiplier) value for IN_3.
12
GRANT_DENY
None
Options for controlling access of host computers and local control panels to
operating, tuning, and alarm parameters of the block. Not used by the device.
14
IN
Determined by source or
EU of PV _SCALE
The analog input value and status. The number of inputs is an extensible parameter
in some function blocks.
16
IN_1
Determined by supplying
block or source.
The first analog input value and status.
17
IN_2
Determined by supplying
block or source.
The second analog input value and status.
18
IN_3
Determined by supplying
block or source.
The third analog input value and status.
15
IN_LO
None
The value used for the input whenever IN is below range.
13
INPUT_OPTS
None
Sets the options for using IN, IN_LO, IN_1, IN_2 and IN_3 when any are either Bad
or Uncertain.
5
MODE_BLK
None
The mode record of the block. MODE contains the actual, target, permitted, and
normal modes. In some function blocks, this parameter is used to request and show
the source of the setpoint, the source of the output, and/or the block operating state.
8
OUT
EU of OUT_SCALE or
Percent or EU of IN
The analog output value and status. The number of outputs is an extensible
parameter in some blocks.
33
OUT_HI_LIM
EU of OUT_SCALE
Supplied by IN
The maximum output value allowed.
34
OUT_LO_LIM
EU of OUT_RANGE or
Supplied by IN
The minimum output value allowed.
11
OUT_RANGE
None
Range of the output.
9
PRE_OUT
EU of OUT
The pre-trip limit from SP or zero.
7
PV
EU of OUT or EU of
PV_SCALE
The process variable used in block execution and alarm limit detection.
Summary of Contents for OCX 8800
Page 2: ......
Page 4: ......
Page 10: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 ii ...
Page 72: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 4 8 ...
Page 88: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 5 16 ...
Page 100: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 6 12 ...
Page 164: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 7 64 ...
Page 176: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 8 12 ...
Page 213: ......
Page 223: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 10 11 ...
Page 225: ......
Page 262: ...Instruction Manual IM 106 880 Rev 2 1 April 2017 OCX 8800 C 2 ...