SNC 4000 User’s Guide
77
--------------------------------------------------------
Air Inlet Temp Nominal 27 C
IO Processor Temp Nominal 30 C
Input Power: +5 Volts Nominal 5.20 V
Input Power: +12 Volts Nominal 12.25 V
Local Power: +2.5 Volts Nominal 2.48 V
Local Power: +3.3 Volts Nominal 3.29 V
Fan Nominal 3245 RPM
All Power Nominal
All Temp. Nominal
Sample Count 2158
value = 1 = 0x1
snc4000 > envMonRangeShow
Air Inlet Temp (C):
Nominal: 5 to 45
Warning: 4 <= N < 5 or 45 < N <= 50
Alarm: N < 4 or N > 50
IO Processor Temp (C):
Nominal: 5 to 80
Warning: 4 <= N < 5 or 80 < N <= 108
Alarm: N < 4 or N > 108
Input Power: +5 Volts (V):
Nominal: 4.94 to 5.35
Warning: 4.83 <= N < 4.94 or 5.35 < N <= 5.46
Alarm: N < 4.83 or N > 5.46
Input Power: +12 Volts (V):
Nominal: 11.62 to 12.62
Warning: 11.50 <= N < 11.62 or 12.62 < N <= 12.87
Alarm: N < 11.50 or N > 12.87
Local Power: +2.5 Volts (V):
Nominal: 2.40 to 2.58
Warning: 2.36 <= N < 2.40 or 2.58 < N <= 2.62
Alarm: N < 2.36 or N > 2.62
Local Power: +3.3 Volts (V):
Nominal: 3.20 to 3.39
Warning: 3.13 <= N < 3.20 or 3.39 < N <= 3.46
Alarm: N < 3.13 or N > 3.46
Fan (RPM):
Nominal: 2520 to 3780
Warning: 2205 <= N < 2520 or 3780 < N <= 4095
Alarm: N < 2205 or N > 4095
value = 1 = 0x1
envMonRangeShow
The
envMonRangeShow
command specifies operational ranges for the SNC 4000's environmental
channels. It displays ranges of values associated with the Nominal, Warning, and Alarm states for voltage,
temperature, and fan/blower operation according to the channels defined in the
envMonShow
command:
Summary of Contents for SNC 4000
Page 1: ...www adic com ADICSNC 4000User sGuide ADVANCED DIGITAL INFORMATION CORPORATION...
Page 10: ...4 SNC 4000 Introduction...
Page 40: ...34 Removal and Replacement Procedures...
Page 140: ...134 Service Port Command Reference...
Page 147: ...SNC 4000 User s Guide 141 fcConnPortModeGet...
Page 148: ...142 Diagnostic Command Reference...