High
−
level Instructions
3
−
487
Caution regarding pulse output function (F168 and F169)
Use a program such as the following when performing continuous motor rotation in one direction.
R0
F1 DMV, K0,
DT9044
F0 MV, H2,
DT0
F0 MV, K1000,
DT1
F0 MV, K7000,
DT2
F0 MV, K300,
DT3
F1 DMV, K100000, DT4
X0
R0
DF
F0 MV, K0,
DT6
F168 SPD1, DT0, K0
Clear the elapsed value
Incremental control
Initial speed
Maximum speed
Acceleration/deceleration time
Target value (Movement amount)
Positioning start
Pulse output stops when the upper limit of the internal elapse value is exceeded if rotation is in one direction
only.
As a countermeasure, reset the elapsed value (zero clear) before executing
F168 (SPD1)
or
F169 (PLS)
instructions, as with the program, above.
The pulse output does not stop when the FP0R is used as the FP0 (FP0 compatibility mode).
The elapsed value is signed 32
−
bit value.
FP0/FP
−
e