5-53
WR904 FP0R
Relay
No.
Name
Description
R9040
TOOL port
operation mode
flag
-
Turns on when the general-purpose communication function is being
used
-
Goes off when the computer link function is being used.
R9041
COM port PLC
link flag
Turn on while the PLC link function is used.
R9042 Not
used
R9043 Not
used
R9044
COM port
SEND/RECV
instruction
execution flag
Monitors whether the F145 (SEND) or F146 (RECV) instructions can
be executed or not.
Off: None of the above mentioned instructions can be executed.
(During executing the instruction)
On: One of the above mentioned instructions can be executed.
R9045
COM port
SEND/RECV
instruction
execution end
flag
Monitors if an abnormality has been detected during the execution of
the F145 (SEND) or F146 (RECV) instructions as follows:
Off: No abonormality detected.
On: An abnormality detected. (communication error)
End code: DT90124
R9046 Not
used
R9047 Not
used
R9048 Not
used
R9049 Not
used
R904A Not
used
R904B Not
used
R904C
to R904F
Not used
A: Available, N/A: Not available
Note) R9040 to R904F can be changed during 1 scan.
WR905 FP0R
Relay
No.
Name
Description
R9050
MEWNET-W0
PLC link
transmission
error flag
When using MEWNET-W0
-
Turns on when a transmission error occurs at PLC link.
-
Turns on when there is an error in the PLC link area settings.
R9051 to
R905F
Not used
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...