5-46
FP0R
No.
Name
Default
value
Descriptions
CH0:
Normal
output
Normal output (Y0, Y1)
Pulse output (Y0, Y1)
Pulse output (Y0, Y1)/Home input X4
Pulse output (Y0, Y1)/Home input X4/Position
control starting input X0
PWM output (Y0), Normal output (Y1)
CH1:
Normal
output
Normal output (Y2, Y3)
Pulse output (Y2, Y3)
Pulse output (Y2, Y3)/Home input X5
Pulse output (Y3, Y4)/Home input X5/Position
control starting input X1
PWM output (Y2), Normal output (Y3)
CH2:
Normal
output
Normal output (Y4, Y5)
Pulse output (Y4, Y5)
Pulse output (Y4, Y5)/Home input X6
Pulse output (Y4, Y5)/Home input X6/Position
control starting input X2
PWM output (Y4), Normal output (Y5)
T
ran
sisto
r typ
e
C16 o
r o
ver
Controlle
r out
put s
e
ttings
2
(PLS/PWM)
402
Pulse/
PWM output
settings
(Y0 to Y7)
CH3:
Normal
output
Normal output (Y6, Y7)
Pulse output (Y6, Y7)
Pulse output (Y6, Y7)/Home input X7
Pulse output (Y6, Y7)/Home input X7/Position
control starting input X3
PWM output (Y6), Normal output (Y7)
403
Pulse catch
input settings
Not set
The pressed contact is set for the pulse catch.
Inter-
rupt/
Pulse
catch
settings
404
Interrupt input
settings
Not set
The pressed contact is set for the interrupt input.
Inter-
rupt
edge
settings
405
Interrupt edge
setting for
controller input
Leading
edge
The pressed contact is up and set to trailing edge.
Note1) When using the pulse output/PWM output, the controller output settings must be specified.
The output that has been set to the pulse output/PWM output cannot be used as the normal
output.
Note2) X4 to X7 can be used as the home input of the pulse output CH0 to CH3.
When using the home return function of the pulse output, always set the home input. In that
case, X4 to X7 cannot be set as the high-speed counter.
Note3) C16 type:
- For performing the home return for the pulse output CH0 with deviation counter clear, the
above Y6 should be set to the normal output to use Y6 for the deviation counter clear signal.
- For performing the home return for the pulse output CH1 with deviation counter clear, the
above Y7 should be set to the normal output to use Y7 for the deviation counter clear signal.
- The home return cannot be performed for the pulse output CH2 with deviation counter clear.
Note4) C32/T32/F32 type:
When performing theo home return with deviation counter clear, the deviation counter clear
signals corresponding to each CH are used fixedly as follows; CH0=Y8, CH1=Y9, CH2=YA,
CH3=YB
For performing the home return for each type,
it is necessary to specify the home input corresponding to each channel to be used for the home
return in the system register 401.
Home input corresponding to each channel: CH0=4, CH1=X5, CH2=X6, CH3=X7
For performing the JOG positioning for each type,
it is necessary to specify the position control starting input signal corresponding to each channel
to be used for the JOG positioning.
Note3) The settings for pulse catch and interrupt input can only be specified in system registers 403 to
405.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...