High
−
level Instructions
3
−
280
Outline
Rotates a specified number of bits in the specified 16-bit data to the left
together with carry flag data.
For the FP0R/FP
Σ
/FP
−
X/FP0/FP
−
e, the P type high
−
level instruction
“P123 (PRCL)” is not available.
Program example
Ladder Diagram
Boolean
Ladder Diagram
Address
Instruction
10
F123 RCL , DT 0 , K 4
D
n
Trigger
R0
10
11
ST
R
0
F123
(RCL)
DT
0
K
4
D
16-bit area
n
16-bit equivalent constant or 16-bit area to specify number of bits to be rotated
Operands
Operand
Relay
Timer/Counter
Register
Index
register
Constant
Index
Operand
WX WY WR WL
(
*
1)
SV
EV
DT LD
(
*
1)
FL
(
*
2)
IX
(
*
3)
IY
(
*
4)
K
H
Index
modifier
D
N/A
A
A
A
A
A
A
A
A
A
A
N/A N/A
A
n
A
A
A
A
A
A
A
A
A
A
A
A
A
A
(
*
1) This cannot be used with the FP0 and FP
−
e.
(
*
2) This cannot be used with the FP0, FP
−
e, FP0R, FP
Σ,
FP
−
X.
(
*
3) With the FP0R, FP
Σ
, FP
−
X, FP2, FP2SH, and FP10SH, this is I0 to IC.
(
*
4) With the FP0R, FP
Σ
, FP
−
X, FP2, FP2SH, and FP10SH, this is ID.
Explanation of example
Rotates 4 bits in data register DT0 together with carry flag data “1” to the left when trigger R0 turns on.
0 1
0 1
1 0
0 0
R0: on
· ·
·
Bit position
·
· ·
· ·
DT0
15
0
12
0
11
0
8
1
7
0
4
0
3
1
0
0
Data in bit position 12
Carry flag data “1”
1
Special internal relay
R9009 (carry flag)
· ··
·
Bit position
·
· ·
· ·
DT0
15
0 0 0
12
1
11
0 0 1
8
0
7
0 0 1
4
1
3
0 1 0
0
0
F123
P123
(PRCL)
(RCL)
16-bit data left rotation with carry flag data
A: Available
N/A: Not Available
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...