Basic Instructions
2
−
30
Outline
When a leading edge of signal is detected, the contact goes on during
that scan only. Leading edge detection is possible at the first scan.
Program example
Ladder Diagram
Boolean
Ladder Diagram
Address
Instruction
DFI
X0
0
Y10
Leading edge differential
(initial execution type)
0
1
3
ST
X
0
DFI
OT
Y
10
Explanation of example
Output to Y10 takes place for one scan only following a change in X0 from off to on.
When the trigger X0 is met after RUN is begun
X0
Y10
Leading edge
One scan
When the trigger X0 is met before RUN
X0
Y10
One scan
Description
When the trigger (execution condition) changes from off to on, the
DFI
instruction outputs (differential output)
during the following scan only.
When the trigger (execution condition) is met before RUN is begun, output (differential output) takes place at
the first scan.
There is no limit to the number of times the
DFI
instruction can be used.
When the mode is changed to RUN or the power is turned on in RUN mode and the trigger (execution
condition) is already met, a
DF
instruction will not obtain output at the first scan. For this reason, use a
DFI
instruction.
DFI
Leading edge differential
(initial execution type)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...