3
−
643
Outline
Calculates the total and mean numbers in the specified word data table.
For the FP0R/FP
Σ
/FP
−
X, the P type high
−
level instruction “P275
(PMEAN)” is not available.
Program example
Ladder Diagram
Boolean
Ladder Diagram
Address
Instruction
S1
Trigger
D
S2
F275 MEAN, DT10, DT20, DT30
10
R10
10
11
ST
X
10
F275
(MEAN)
DT
10
DT
20
DT
30
S1
Starting 16-bit area of data table
S2
Ending 16-bit area of data table
D
Starting 16-bit for storing total and mean numbers (3 words)
Operands
Operand
Relay
Timer/Counter
Register
Index
register
Constant
Index
modifier
Integer
device
Operand
WX WY WR WL
SV
EV
DT LD
FL
I
K
H
f
modifier device
S1
A
A
A
A
A
A
A
A
A
A
N/A N/A N/A
A
N/A
S2
A
A
A
A
A
A
A
A
A
A
N/A N/A N/A
A
N/A
D
N/A
A
A
A
A
A
A
A
A
A
N/A N/A N/A
A
N/A
Description
The total value and the average value of the word data (signed) from the area selected with S1 to the area
selected with S2 are obtained and stored in the area selected with D.
Total (32 bits)
Mean (16 bits)
15
0
D
D+1
D+2
Decimals of the average value are rounded off so that the average value is an integer.
F275
P275
(PMEAN)
(MEAN)
Total and mean numbers calculation in 16-bit data table
A: Available
N/A: Not Available
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...