High
−
level Instructions
3
−
504
Outline
Outputs pulses from the specified pulse output channels according to
the specified parameters.
[Feature] An acceleration time and deceleration time can be set
respectively. Also, the deceleration stop is available.
The target speed can be changed.
Program example
Ladder Diagram
Boolean
Ladder Diagram
Address
Instruction
F171 SPDH , DT100 , K 0
S
n
R10
DF
To change the speed, do not insert the DF instruction
as the trigger should be kept being ON.
10
11
12
ST
R
10
DF
F171
(SPDH)
DT
100
K
0
S
Starting 16
−
bit area for registering data tables
n
Channels intended for pulse output (n=0 to 3)
Operands
Operand
Relay
Timer/Counter Register
Index
register
SWR
SDT
Constant
Index
modifier
Operand
WX WY WR WR
SV
EV
DT
In (*1)
SWR
SDT
K
H
modifier
n
N/A N/A N/A N/A
N/A
N/A
A
N/A
N/A
N/A
N/A N/A
A
S
N/A N/A N/A N/A
N/A
N/A
N/A
N/A
N/A
N/A
A
A
N/A
(
*
1) I0 to ID
Description
When the trigger is on, pulses are output from the specified channels and the trapezoidal control can be
performed.
The control code, initial speed, target speed, acceleration time, deceleration time and the target value is
specified by creating data tables [S] to [S+11] using user progrmas.
When accelerating, the frequency is changed in the acceleration time specified from the initial speed to the
target speed.
When decelerating, the frequency is changed in the deceleration time specified from the target speed.
The deceleration stop request is available by the control data (bit5) of DT90052. (e.g.) F0(MV) H120,
DT90052
When using the same condition as the table used at the preveious startup, the operation can be started at
high speed without calculation.
Method of acceleration/deceleration and initial speed
During the pulse output, the pulse output insturction flag corresponding to the channel turns on.
When the deceleration stop is requested during acceleration, deceleration is performed with the same slope
of the deceleration time from the target speed.
In this instruction, the operation is processed giving the acceleration/deceleration time priority.
FP0R
Pulse output
(Trapezoidal control)
5
F171
(SPDH)
Availability
FP0R
A: Available
N/A: Not Available
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...