3.1
Composition of High-level Instructions
3 - 5
3.1.3
High-level Instruction and Execution Condition (Trigger)
A high-level instruction is always used in a pair with its execution condition (trigger).
When the operation result of the relay sequence circuit specified as the execution
condition (trigger) is on, the high-level instruction is executed.
Example:
When the execution condition (trigger) X0 is on, the F0 (MV)
instruction is executed and K0 is transferred to DT0.
F0 MV, K0, DT0
X0
Execution condition
(Trigger)
There is no need to program the same execution condition (trigger) many times when
two or more high-level instructions are programmed consecutively with the same
execution condition (trigger).
Example:
F0 MV, K50, DT1
X0
This execution condition (trigger) is not required.
F151 WRT, K0, DT1, K1, K0
X0
F0 MV, K50, DT1
X0
F151 WRT, K0, DT1, K1, K0
Precautions if omitting execution conditions (triggers)
If you need to program both “F” and “P” type high-level instructions using the same
execution condition (trigger), proceed according to one of the following two examples.
Example 1: The same execution condition (trigger) is programmed twice for
“F” and “P” type instructions.
F0 MV, DT 0 , DT 1
P0 PMV, H 8000, DT 9058
F0 MV, DT 2 , DT 3
F60 CMP, DT 1 , DT 3
P157 PCADD, DT 9054, DT 0, DT 30
X0
X0
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 2: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 24: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 1333: ...5 245 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...